TrakMax 40 User Manual
Revision 1.0
windynation
TrakMax 40
MPPT Solar Charge Controller
CHC-TRMX-40
User’s Manual
Page 1 of 20
windynation
03/06/2013
Vista de página 0
1 2 3 4 5 6 ... 19 20

Resumo do Conteúdo

Página 1 - TrakMax 40

TrakMax 40 User Manual Revision 1.0 windynation TrakMax 40 MPPT Solar Charge Controller CHC-TRMX-40 User’s Manual Page 1 of 20 windynati

Página 2

TrakMax 40 User Manual Revision 1.0 3.5 OVERCURRENT PROTECTION Circuit breakers or fuses must be installed in both the battery and solar circuits

Página 3 - 1 INTRODUCTION

TrakMax 40 User Manual Revision 1.0 3.8 COMMUNICATION PORT Network connections allow the TrakMax to communicate with other controllers or compute

Página 4 - 1.5 LIMITATION OF LIABILITY

TrakMax 40 User Manual Revision 1.0 Battery Type 12 Volt Units 24 Volt Units Lead Acid 0.03 volts (30mv) per degree Celsius 0.06 volts (60mv) pe

Página 5 - 2 PRODUCT OVERVIEW

TrakMax 40 User Manual Revision 1.0 power, than a hot PV array. When PV voltage is sufficiently high for MPPT to operate, a constant power output

Página 6

TrakMax 40 User Manual Revision 1.0 4.2.2 Three Stage Charge The TrakMax is configured for a three stage charging process, Bulk, Absorption and F

Página 7 - 3 INSTALLATION

TrakMax 40 User Manual Revision 1.0 5) Reset the BATTERY TYPE SELECTOR potentiometer to the appropriate setting for the system batteries when the

Página 8 - 3.4 CONNECTIONS

TrakMax 40 User Manual Revision 1.0 • Equalize: During an equalization cycle, the charging voltage will be held constant at the specified voltage

Página 9

TrakMax 40 User Manual Revision 1.0 A solid green LED indicates the charging source is functioning properly. A flashing green LED indicates an er

Página 10 - 3.7 PARALLEL CONNECTION

TrakMax 40 User Manual Revision 1.0 5.2.1 Low Voltage Disconnect (LVD) When a DC load is connected, if voltage remains below the Low Voltage Disc

Página 11 - 3.8 COMMUNICATION PORT

TrakMax 40 User Manual Revision 1.0 automatically when the unit first receives power. PV open circuit voltage must be 12-30VDC for 12VDC battery c

Página 12 - 4 OPERATION

TrakMax 40 User Manual Revision 1.0 Table of Contents 1 Introduction ...

Página 13 - 4.2 CHARGE MODE

TrakMax 40 User Manual Revision 1.0 batteries and are rated at 80 to 100 amp-hours at 12volts. Many larger systems use L16 batteries, which are us

Página 14

TrakMax 40 User Manual Revision 1.0 1 INTRODUCTION Windy Nation Inc. (“Windy Nation”) is not assembling the wind unit, installing the solar syst

Página 15 - 4.4 BATTERY SELECTION

TrakMax 40 User Manual Revision 1.0 defective Product to repair or replace such Product. If a warranty claim is invalid for any reason, the Custom

Página 16 - 5 LED INDICATORS

TrakMax 40 User Manual Revision 1.0 2 PRODUCT OVERVIEW The TrakMax solar charge controller is a 40 amp 12/24 Volt Maximum Power Point Tracking (M

Página 17 - 5.2 LED MODES

TrakMax 40 User Manual Revision 1.0 Overload Protection (DC load) 2.0*Inom>5s 1.5*Inom >20s 1.25*Inom temperature controlled Bulk Charge (a

Página 18 - 6.2 TROUBLESHOOTING

TrakMax 40 User Manual Revision 1.0 3 INSTALLATION  Insure all terminating connections are clean and tight to prevent arcing and overheating. 

Página 19 - 7 BATTERIES

TrakMax 40 User Manual Revision 1.0 3.3 GROUNDING The TrakMax is designed to work with grounded electrical systems. In the controller, ground is

Página 20 - 7.3 EQUALIZATION CHARGING

TrakMax 40 User Manual Revision 1.0 3) Terminal connectors for DC wiring are located on the lower edge of the circuit board. Once t